WireFormulaNEC calculators
2023 NEC · Free · No signup

Electrical calculators that show the code behind the answer

Wire size, ampacity, conduit fill, breaker size, voltage drop, and box fill — all built on the same NEC tables your inspector uses. Every result names the table and the rule that produced it.

Six calculators, one wiring model

Why a shared engine matters

Wire sizing, ampacity, conduit fill, voltage drop, and box fill all read from the same conductor table. Change the insulation rating in one place and every downstream answer moves with it, which is how the code actually works — a 90 °C THHN conductor does not become a 60 °C NM-B conductor just because a calculator is looking at it.

Most free calculators treat each tool as a separate lookup. Here the five questions — what ampacity, what breaker, what conduit, what drop, what box — resolve against one dataset.

  • 230+conductor, conduit, and breaker combinations
  • 63pre-rendered pages — no server, no database
  • 5NEC articles cited inline with every result
  • 0third-party scripts in the calculators

Reference charts

Common questions

Are these calculators based on the 2023 NEC?

Yes. Tables 310.16, 240.6(A), 250.122, 314.16(B), and Chapter 9 Tables 1, 4, 5, and 8 come from the 2023 National Electrical Code. Local amendments and older code cycles can differ, so confirm with your authority having jurisdiction.

Do I need to create an account?

No. Every calculator runs in your browser, works without a signup, and keeps working offline once the page has loaded.

Why does the wire size calculator show a smaller conductor than my electrician used?

The NEC value is a minimum under the conditions you entered. Electricians often go up a size for voltage drop, for future load, because the terminals are only rated 60 °C, or because of local amendments. Enter your actual wire type and ambient temperature to see the code minimum.

Is voltage drop a code requirement?

Voltage drop limits are recommendations in 210.19(A) Informational Note 4 and 215.2(A) Informational Note 2 (3% on a branch circuit, 5% total). They become mandatory for specific installations such as fire pumps. Many inspectors still expect you to stay within them.

Values in these tools come from the 2023 National Electrical Code and are provided for planning and study. They are not a substitute for the adopted code in your jurisdiction or for a licensed electrician. Read the full disclaimer.