Wire Ampacity Chart
Allowable ampacities for copper and aluminum conductors in amperes, based on not more than three current-carrying conductors in a raceway, cable, or earth, at an ambient temperature of 30 °C. For other conditions, apply the correction and adjustment tables below.
| Size | Cu 60 °C | Cu 75 °C | Cu 90 °C | Al 60 °C | Al 75 °C | Al 90 °C |
|---|---|---|---|---|---|---|
| 14 AWG | 15 | 20 | 25 | — | — | — |
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 |
| 8 AWG | 40 | 50 | 55 | 35 | 40 | 45 |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 |
| 1/0 AWG | 125 | 150 | 170 | 100 | 120 | 135 |
| 2/0 AWG | 145 | 175 | 195 | 115 | 135 | 150 |
| 3/0 AWG | 165 | 200 | 225 | 130 | 155 | 175 |
| 4/0 AWG | 195 | 230 | 260 | 150 | 180 | 205 |
| 250 kcmil | 215 | 255 | 290 | 170 | 205 | 230 |
| 300 kcmil | 240 | 285 | 320 | 195 | 230 | 260 |
| 350 kcmil | 260 | 310 | 350 | 210 | 250 | 280 |
| 400 kcmil | 280 | 335 | 380 | 225 | 270 | 305 |
| 500 kcmil | 320 | 380 | 430 | 260 | 310 | 350 |
| 600 kcmil | 350 | 420 | 475 | 285 | 340 | 385 |
| 700 kcmil | 385 | 460 | 520 | 315 | 375 | 425 |
| 750 kcmil | 400 | 475 | 535 | 320 | 385 | 435 |
| 900 kcmil | 435 | 520 | 585 | 355 | 425 | 480 |
| 1000 kcmil | 455 | 545 | 615 | 375 | 445 | 500 |
2023 NEC Table 310.16. Values in amperes. 18 and 16 AWG fixture wire are covered by Table 402.5, not 310.16.
How to use the chart
Find the conductor size, read across to the temperature column that matches the insulation and the termination rating, then apply the correction factors. The 90 °C column is used for adjustment calculations, but 110.14(C) usually caps the final answer at the termination temperature — 75 °C for most modern breakers, 60 °C for older equipment and for NM-B cable.
Use the ampacity calculator to apply both corrections at once and see the usable value.
Ambient temperature correction
Multiply the base ampacity by the factor for the ambient temperature at the conductor — not the outdoor temperature, and not the thermostat setting. A conduit in a sunny attic runs much hotter than the air temperature reported by a weather app.
| Ambient temperature | 60 °C conductor | 75 °C conductor | 90 °C conductor |
|---|---|---|---|
| ≤ 10 °C (50 °F) | 1.29 | 1.20 | 1.15 |
| 11–15 °C | 1.22 | 1.15 | 1.12 |
| 16–20 °C | 1.15 | 1.11 | 1.08 |
| 21–25 °C | 1.08 | 1.05 | 1.04 |
| 26–30 °C | 1.00 | 1.00 | 1.00 |
| 31–35 °C | 0.91 | 0.94 | 0.96 |
| 36–40 °C | 0.82 | 0.88 | 0.91 |
| 41–45 °C | 0.71 | 0.82 | 0.87 |
| 46–50 °C | 0.58 | 0.75 | 0.82 |
| 51–55 °C | 0.41 | 0.67 | 0.76 |
| 56–60 °C | — | 0.58 | 0.71 |
| 61–65 °C | — | 0.47 | 0.65 |
| 66–70 °C | — | 0.33 | 0.58 |
| 71–75 °C | — | — | 0.50 |
| 76–80 °C | — | — | 0.41 |
| 81–85 °C | — | — | 0.29 |
NEC Table 310.15(B)(1), 30 °C base. A dash means that insulation rating is not permitted at that ambient temperature.
Conductor bundling adjustment
When more than three current-carrying conductors share a raceway or cable, Table 310.15(C)(1) reduces ampacity. Count only current-carrying conductors — a neutral that carries only the unbalanced current of a linear load does not count.
| Current-carrying conductors | Adjustment factor |
|---|---|
| 1–3 | 1.00 |
| 4–6 | 0.80 |
| 7–9 | 0.70 |
| 10–20 | 0.50 |
| 21–30 | 0.45 |
| 31–40 | 0.40 |
| 41+ | 0.35 |
NEC Table 310.15(C)(1). Applies after ambient correction.
Copper versus aluminum
Aluminum sits about two sizes behind copper: 4 AWG aluminum carries roughly what 6 AWG copper carries. The gap narrows at large sizes, which is why service entrance and feeder work often uses aluminum while branch circuits stay copper. Aluminum also starts at 12 AWG in Table 310.16 — 14 AWG aluminum is not listed.
Ampacity is only one of three checks. The conductor also has to satisfy the overcurrent protection rules in Article 240 and, on long runs, voltage drop.