WireFormulaNEC calculators
NEC Chapter 9

Conduit Fill Chart

Maximum number of THHN or THWN conductors that fit in each trade size at the 40% fill limit for three or more conductors. A dash means the conductor does not fit even as a single conductor.

These tables are calculated from Table 5 conductor areas and Table 4 raceway areas, not copied from a manufacturer chart. Different conductor types have different areas — compact stranded THHN and some XHHW-2 conductors will fit more than the table shows.

EMT — electrical metallic tubing

Trade size14 AWG12 AWG10 AWG8 AWG6 AWG4 AWG2 AWG1/0 AWG4/0 AWG
1/2 in12953111——
3/4 in21161054211—
1 in352516964211
1-1/4 in61442816117531
1-1/2 in83613822169741
2 in138100633626161174
2-1/2 in24117611164462820127
3 in364266167966942301910
3-1/2 in4763472181269156392414
4 in60844327916111671503118

Maximum THHN/THWN conductors in EMT at 40% fill (2023 NEC Chapter 9, Tables 1, 4, and 5).

PVC Schedule 40

Trade size14 AWG12 AWG10 AWG8 AWG6 AWG4 AWG2 AWG1/0 AWG4/0 AWG
1/2 in11853111——
3/4 in2015954111—
1 in342515964211
1-1/4 in59432715117531
1-1/2 in81593721159641
2 in13598623525151174
2-1/2 in1931418951372216105
3 in29921813779573525158
3-1/2 in4012921841067647332012
4 in5173772371379960432715

Maximum THHN/THWN conductors in PVC Schedule 40 at 40% fill.

PVC Schedule 80

Trade size14 AWG12 AWG10 AWG8 AWG6 AWG4 AWG2 AWG1/0 AWG4/0 AWG
1/2 in864111———
3/4 in1612743111—
1 in282013753111
1-1/4 in5137231396421
1-1/2 in70513218138531
2 in1188654312213963
2-1/2 in169123784532191485
3 in26519312270503122137
3-1/2 in358261164946842301810
4 in4643382131238854382413

PVC 80 has thicker walls than PVC 40, so it holds fewer conductors at the same trade size.

IMC and rigid metal conduit

Trade size14 AWG12 AWG10 AWG8 AWG6 AWG4 AWG2 AWG1/0 AWG4/0 AWG
1/2 in12953111——
3/4 in22161064211—
1 in362616964311
1-1/4 in62452816127531
1-1/2 in856239221610741
2 in140102643726161174
2-1/2 in2001469253382316106
3 in30922514281593625169
3-1/2 in4123011891097848342112
4 in53138724414010162442715

Maximum THHN/THWN conductors in rigid metal conduit at 40% fill. IMC is slightly larger internally.

Internal area by raceway type

Fill is a ratio of areas. These are the total internal areas from Table 4 that every calculation starts from.

Trade sizeEMTPVC 40PVC 80IMCRMC
1/2 in0.3040.2850.2170.3420.314
3/4 in0.5330.5080.4090.5860.549
1 in0.8640.8320.6880.9590.887
1-1/4 in1.4961.4531.2371.6471.526
1-1/2 in2.0361.9861.7112.2252.071
2 in3.3563.2912.8743.6303.408
2-1/2 in5.8584.6954.1195.1354.866
3 in8.8467.2686.4427.9227.499
3-1/2 in11.5459.7378.68810.58410.010
4 in14.75312.55411.25813.63112.882

Total internal area in square inches, NEC Chapter 9 Table 4.

Reading the chart

The values assume the 40% limit that applies to three or more conductors. If you are checking one conductor, the limit is 53%; for two, it is 31%; for a nipple 24 inches or less, it is 60%. The conduit fill calculator applies the correct limit automatically.

A count of nine 12 AWG THHN conductors in 1/2 inch EMT is the number most electricians memorize. It is correct, and it is also close to the limit — ten conductors would exceed 40%.

Why the chart and the calculator can disagree

Conductor area depends on the specific wire. THHN, THWN-2, XHHW-2, and compact stranded versions of the same size all have different areas. Table 5 lists several; this chart uses the standard THHN/THWN value. When a job is tight, use the actual manufacturer's area.